电力系统自动化2012,Vol.36Issue(22):120-122,3.
单母线分段接线中备用电源自动投入装置的改进
Improvement of Automatic Transfer Switch for Backup Power Supply Used in Sectionalized Single-bus Configuration
苏宜强 1孔璐 1伏祥运 1李一磊2
作者信息
- 1. 江苏省电力公司连云港供电公司,江苏省连云港市222004
- 2. 南京供电公司,江苏省南京市210008
- 折叠
摘要
Abstract
The 110 kV substation often equips with automatic transfer switch (ATS) for backup power supply in order to ensure the reliability of power supply. If the circuit breaker rejects operation when ATS operates, it may cause the power supply failure of the whole station. The power supply failure of 110 kV substation has been analyzed. Operation logic shortcomings of normal ATS are pointed out, and an improved scheme of incoming line ATS is proposed.关键词
单母线分段接线/备用电源/自动投入装置/开关拒动/供电可靠性/全站停电Key words
sectionalized single-bus configuration/backup power supply/automatic transfer switch/switch operation rejection/power supply reliability/power supply failure of whole station分类