电网技术2012,Vol.36Issue(9):262-267,6.
220kV隔离开关地震模拟振动台试验
Shake Table Test on 220 kV Disconnecting Switch
摘要
Abstract
As a key component of power transmission and distribution systems, disconnecting switches have suffered serious damage in previous earthquakes. Generally, typical destruction feature of disconnecting switches during earthquakes appears as the breaking at bottom of insulator porcelain posts. In this paper, shake table test on a full-scale disconnecting switch was carried out to study the seismic behavior of the equipment. Displacements, strains and accelerations of the critical parts of the equipment were measured under broadband white-noise tests and input ground motions. The influence of the supporting frame and blades on seismic responses of insulators was estimated. The test results indicate that the responses of the two insulators in the disconnecting switch are correlated, and the amplification factors of the supporting frame are larger than that specified in the specifications.关键词
隔离开关/振动台试验/地震响应/相关性/放大系数Key words
disconnecting switch/ shake table test/ seismic response/ correlation/ amplification factor分类
信息技术与安全科学引用本文复制引用
谢强,朱瑞元,周勇,杨雯,王亚非..220kV隔离开关地震模拟振动台试验[J].电网技术,2012,36(9):262-267,6.基金项目