| 注册
首页|期刊导航|电网技术|±1100kV特高压直流输电换流站内深度限制过电压水平研究

±1100kV特高压直流输电换流站内深度限制过电压水平研究

姬大潜 刘泽洪 张进 张翠霞 朱艺颖

电网技术2012,Vol.36Issue(10):55-60,6.
电网技术2012,Vol.36Issue(10):55-60,6.

±1100kV特高压直流输电换流站内深度限制过电压水平研究

Research on Overvoltage Limitation Inside ±1100 kV UHVDC Converter Station

姬大潜 1刘泽洪 2张进 2张翠霞 1朱艺颖1

作者信息

  • 1. 中国电力科学研究院,北京市海淀区100192
  • 2. 国家电网公司,北京市西城区100031
  • 折叠

摘要

Abstract

Insulation coordination inside the converter station is one of the key technologies for ±1 100 kV UHVDC power transmission project and it is of significance to reduce the manufacturing difficulty of related equipments. A model for the simulation and calculation of ±1 100 kV UHVDC power transmission project is proposed; and steady-state operation voltage and switching impulse of ±1 100 kV UHVDC system are simulated and summarized. Based on the ageing test of arrester performance, the feasibility of reducing insulation level of equipments by high-performance arresters is presented in detail, and recommended values of impulse insulation levels and insulation margins of equipments for ±1 100 kV UHVDC power transmission project are given.

关键词

±1100kV直流输电/过电压/绝缘配合/避雷器

Key words

±1 100 kV UHVDC power transmission project/ overvoltage/ insulation coordination/ arrester

分类

信息技术与安全科学

引用本文复制引用

姬大潜,刘泽洪,张进,张翠霞,朱艺颖..±1100kV特高压直流输电换流站内深度限制过电压水平研究[J].电网技术,2012,36(10):55-60,6.

电网技术

OA北大核心CSCDCSTPCD

1000-3673

访问量0
|
下载量0