中国感染控制杂志2012,Vol.11Issue(5):372-373,369,3.
医院管道直饮水用户端细菌污染控制研究
Control of bacterial contamination on direct drinking water in a hospital
伍俊玲 1周艳华1
作者信息
- 1. 湖南省肿瘤医院,湖南,长沙,410013
- 折叠
摘要
Abstract
Objective To explore bacterial contamination of direct drinking water system in a hospital. Methods From January 2011 to February 2012, random sampling of finished water, drinking water on client-server and inner surface of outlet of drinking water machine in a hospital were taken and performed bacterial culture. Results Through the formulation of management system and standardization of operation, maintenance, cleaning and disinfection process of drinking water system, the qualified rate of finished water, drinking water on client-server, and bacterial culture of inner surface of outlet increased from 93. 33% (28/30)to 100. 00%(90/90) , 89. 80%(88/98) to 98. 91%(182/184) , and 91. ll%(41/45) to 100. 00% (150/150)respectively (all P<0. 05). Conclusion Bacterial contamination existed in finished water and drinking water on client-server, strengthening the standardized disinfection management of drinking water pipes and the client-servers can effectively improve the qualified rate of direct drinking water.关键词
管道直饮水系统/细菌污染/饮水/感染控制/水源性感染Key words
drinking water system/ bacterial contamination/ drinking water/ infection control/ waterborne infection分类
医药卫生引用本文复制引用
伍俊玲,周艳华..医院管道直饮水用户端细菌污染控制研究[J].中国感染控制杂志,2012,11(5):372-373,369,3.