| 注册
首页|期刊导航|高电压技术|Insulation Coordination of ±800 kV UHVDC Xiluodu Converter Station

Insulation Coordination of ±800 kV UHVDC Xiluodu Converter Station

DENG Xu WANG Dongju ZHOU Hao CHEN Xilei XU Anwen SHEN Yang

高电压技术2012,Vol.38Issue(12):3198-3205,8.
高电压技术2012,Vol.38Issue(12):3198-3205,8.

Insulation Coordination of ±800 kV UHVDC Xiluodu Converter Station

Insulation Coordination of ±800 kV UHVDC Xiluodu Converter Station

DENG Xu 1WANG Dongju 1ZHOU Hao 1CHEN Xilei 1XU Anwen 1SHEN Yang2

作者信息

  • 1. College of Electrical Engineering, Zhejiang University, Hangzhou 310027, China
  • 2. Zhejiang Electric Power Design Institute, Hangzhou 310014, China
  • 折叠

摘要

Abstract

The insulation coordination for converter stations in ±800 kV UHVDC projects is one of the key problems to be solved, and it is critical for the design, type selection, manufacture and test of converter station equipments. To specify the insulation levels of converter station equipments in Xiluodu-Zhexi ±800 kV UHVDC project reasonably and to ensure the future work of this UHVDC project can be done smoothly, the insulation coordination of the rectifier side of Xiluodu converter station is studied based on the insulation coordination methods for UHVDC converter station. The configuration scheme of arresters installed in Xiluodu converter station is proposed, and the protective functions for each arrester are analyzed in detail. Then, the arrester parameters and protection levels are calculated. After analyzing the characteristics of UHVDC converter valve, and with reference to experience of the existing UHVDC projects' operation, this paper suggests that the insulation margins of switching, lightning and steep front impulse for converter valve should be 10%, 10%, 15%. Finally, based on the recommended insulation margins and relevant standards, the insulation levels of the converter station is specified: the lightning and switching impulse insulation levels of AC switchyard are 1 550 kV and 1 175 kV, respectively, and for DC bus are 1 950 kV and 1 600 kV, respectively.

关键词

高压直流换流站/特高压直流输电/绝缘配合/溪洛渡/高压直流输电工程/绝缘水平/避雷器/配合方法

Key words

ultra high voltage direct current (UHVDC)/± 800 kV/converter station/arrester/insulationcoordination/insulation level

分类

信息技术与安全科学

引用本文复制引用

DENG Xu,WANG Dongju,ZHOU Hao,CHEN Xilei,XU Anwen,SHEN Yang..Insulation Coordination of ±800 kV UHVDC Xiluodu Converter Station[J].高电压技术,2012,38(12):3198-3205,8.

基金项目

Project supported by National Basic Research Program of China (973 Program) (2011CB209405). ()