中国电机工程学报2012,Vol.32Issue(28):164-170,7.
导线雷电冲击电晕特性试验研究
Experimental Researches on Lightning Impulse Corona Characteristics of Conductors
摘要
Abstract
When lightning strikes at transmission line, the lightning waves will go into the substations along the transmission lines and have great harmful effect on the equipment. In China, the design of equipment lightning insulation often ignores the effect of impulse corona on transmission lines. As the impulse corona could lead great attenuation and distortion to the lightning waves, the margins of the traditional designs are great. In this paper, series experiments were carried out in China UHV AC test base and Q-V characteristic curves of different conductors were got. Results show that as the number of bundle conductors increases, the corona inception voltages increase. The positive impulse corona occurs a little time later than the lightning impulse voltage exceeds the corona inception voltages. In the end of this paper, a corona model based on the test results that could be used in electromagnetic transient calculation software is proposed.关键词
特高压/雷电冲击/分裂导线/电晕笼/冲击电晕/电磁暂态计算Key words
ultra high voltage (UHV)/lightning impulse/bundle conductors/corona cage/impulse corona/electromagnetic transient calculations分类
信息技术与安全科学引用本文复制引用
杨鹏程,徐涛,叶奇明,甘鹏,谢梁,邬雄,陈水明..导线雷电冲击电晕特性试验研究[J].中国电机工程学报,2012,32(28):164-170,7.基金项目