高电压技术2013,Vol.39Issue(2):318-323,6.DOI:10.3969/j.issn.1003-6520.2013.02.009
基于灰关联算法分析环境因素对高海拔±800kV线路绝缘子泄漏电流的影响
Influence of Environmental Factors on Leakage Current of ±800 kV Line Insulators at High Altitudes Based on Grey Relation Analysis
摘要
Abstract
To analyze the influence of environmental factors on leakage current of ±800 kV lines insulators, long-term charged assessment on the ±800 kV line insulators was carried out in the live examination field for UHV DC equipment. We statistically analyzed the leakage current of three material (porcelain, composite, glass) ±800 kV lines insulators under natural pollution condition, figured out the correlation between the environmental factors (environment humidity, temperature, temperature alteration ratio) and the leakage current of insulators based on grey relation analysis, and found out the most important factor influencing the leakage current. The results show that the most significant factors are environment humidity, and the surface humidity is the most important factor, the temperature alteration ratio has a greater influence on leakage current, and the correlation between the leakage current and the environmental factors is similar.关键词
灰关联分析/±800 kV线路绝缘子/泄漏电流/环境因素/在线监测/高海拔Key words
grey relation analysis/ ±800 kV line insulators/ leakage current/ environmental factors/ online monitoring/ high altitude引用本文复制引用
刘云鹏,王亮,郭文义,李锐海,秦春旭..基于灰关联算法分析环境因素对高海拔±800kV线路绝缘子泄漏电流的影响[J].高电压技术,2013,39(2):318-323,6.基金项目
国家重点基础研究发展计划(973计划)(2011CB209401) (973计划)
教育部霍英东教育基金基础性研究课题(121058). (121058)