高压电器2013,Vol.49Issue(2):80-84,5.
500kV并联电抗器现场局部放电试验研究
Study on Spot Test of Partial Discharge for 500 kV Shunt Reactor
刘赟 1叶会生 1单周平 1刘兴文 1段肖力 1黄海波 1万勋1
作者信息
- 1. 湖南省电力公司科学研究院,长沙 410007
- 折叠
摘要
Abstract
Partial discharge test is one of the most effective methods for inspecting the insulation condition of electrical equipment. Compared with partial discharge test of transformer, partial discharge test of reactor has the features of large capacity, complicated testing equipment, difficult shielding, heavy current in testing circuit, and so on. In this paper, the configuration of the testing device for 500 kV shunt reactor, as well as its test method, principle and calculation, is introduced. Test results indicate that the configuration of the testing device meets the requirement for spot test of partial discharge of a 500 kV, 40~60 MV·A reactor.关键词
500kV/并联电抗器/局部放电试验Key words
500 kV/ shunt reactor/ partial discharge test分类
信息技术与安全科学引用本文复制引用
刘赟,叶会生,单周平,刘兴文,段肖力,黄海波,万勋..500kV并联电抗器现场局部放电试验研究[J].高压电器,2013,49(2):80-84,5.