| 注册
首页|期刊导航|高压电器|500 kV断路器断口击穿故障与防护措施分析

500 kV断路器断口击穿故障与防护措施分析

徐党国 李雨 孙云生 刘平 骆立实 张恩伟

高压电器2013,Vol.49Issue(3):59-63,68,6.
高压电器2013,Vol.49Issue(3):59-63,68,6.

500 kV断路器断口击穿故障与防护措施分析

Research on Breaker Breakdown and Protecting Measures of 500 kV Circuit Breakers

徐党国 1李雨 1孙云生 1刘平 1骆立实 1张恩伟1

作者信息

  • 折叠

摘要

Abstract

Four breaker breakdown are discribed in this paper. Either insulation defect or mechanical error may cause breaker breakdown of circuit breakers. And the faults cannot be cleared automatically when breakdown happened due to the system voltage. The fault current of breaker breakdown is quite small than the short circuit current as there is no phase to ground fault. None protection operates immediately when breaker breakdown happens and the electric-arc buries between breakers for few seconds. The circuit breaker and the SF6 gas may be damaged during the arc buries. The protecting devices do not operate until the breakdown between the contacts becomes a phase-to-ground and the fault current increases rapiddly. The circuit breakers of EHV transmission line with parralle reactor and breakers of generator-transformer unit have higher risk of breaker flashover than other circuit breakers. The reason of breaker flashover of circuit breakers are analyzed in this paper. Breaker flashover protection of circuit breaker are introduced to protect the circuit breakers from damagement during breaker breakdown faults. The protection setting and time delay of breaker flashover protection for circuit breaker of transmission lines and generator-transformers are discussed respectively.

关键词

断路器/断口闪络/闪络保护

Key words

circuit breaker/breaker flashover/flashover protection

分类

信息技术与安全科学

引用本文复制引用

徐党国,李雨,孙云生,刘平,骆立实,张恩伟..500 kV断路器断口击穿故障与防护措施分析[J].高压电器,2013,49(3):59-63,68,6.

高压电器

OA北大核心CSCD

1001-1609

访问量0
|
下载量0
段落导航相关论文