110 kV架空输电线路复合材料杆塔的材料、电气和机械特性试验

The Material, Electrical and Mechanical Characteristics Tests of Composite Poles for 110 kV Overhead Transmission Lines

邓世聪 1刘庭 2李汉明 1魏前虎 1胡广生 1刘凯 2肖宾2

作者信息

  • 1. 广东电网公司深圳供电局,广东深圳 518001
  • 2. 国网电力科学研究院,武汉430074
  • 折叠

摘要

Abstract

In order to apply the composite pole to power transmission lines for solving the problems of lightening or polution flashover, it is necessary to test its material, electrical and mechanical characteristics. The test results in this paper are as following: the polyurethane composite can remain its insulativity somehow under the condition of damp or raining, and it can be used for pole to increase the insulation level; the composite pole for 110 kV lines is better than the normal steel tower as its phase-ground clearance is higher of 70%, and its lightning impulsive voltage increases about 75% , as well as its creepage distance of phase-ground increases about 40% in the grounding way of groundingwire extracting along the line direction and going off the tower down to the ground; the phase-ground tolerance voltage of pollution flashover is 2.5 times more than the maximum working voltage; the whole strength of pole can meet the requirements in various load conditions, and its deflection is larger than that of the steel pole. A 110 kV double circuits half-composite pole with two bases has been oprating in network for more than one year well enough.

关键词

复合材料/聚氨酯/输电线路/杆塔/雷击闪络/污闪

Key words

composite materials/ polyurethane/ transmission line/ pole/ lightning flashover/ pollution flashover

分类

信息技术与安全科学

引用本文复制引用

邓世聪,刘庭,李汉明,魏前虎,胡广生,刘凯,肖宾..110 kV架空输电线路复合材料杆塔的材料、电气和机械特性试验[J].南方电网技术,2012,6(z1):4,1.

南方电网技术

OACSTPCD

1674-0629

访问量0
|
下载量0
段落导航相关论文