中国电力2013,Vol.46Issue(3):47-52,6.
考虑配电网保护约束的IIDG准入容量及对策分析
Calculation of Penetration Level for Inverter Interfaced Distributed Generator Considering Protection in Distribution Network Constraints and Related Countermeasures
李亚辉 1康积涛 1叶兰兰1
作者信息
- 1. 西南交通大学电气工程学院,四川成都610031
- 折叠
摘要
Abstract
There are significant differences in output characteristics between inverter interfaced distributed generator (IIDG) and rotating machine when accidents occur in power system. An IIDG' s output model was established based on PQ control strategy considering its limited overcurrent ability, and a qualitative analysis was made on IIDG's influence on relay protection and the short-circuit current calculation formulas containing IIDG was duduced. The maximum penetration level of different access point was obtained according to current protection' s state and compared with the penetration level without considering overcurrent limit. To meet the demand of protection of complicated distribution network with high permeability IIDG, a new fault location algorithm was proposed based on zone division and verified by a case study.关键词
逆变型分布式电源/恒功率控制/配电网/准入容量/区域划分/故障定位Key words
inverter interfaced distributed generator (IIDG)/ PQ control/ distribution network/ penetration level/ zone division/ fault location分类
信息技术与安全科学引用本文复制引用
李亚辉,康积涛,叶兰兰..考虑配电网保护约束的IIDG准入容量及对策分析[J].中国电力,2013,46(3):47-52,6.