重庆大学学报2013,Vol.36Issue(3):109-113,134,6.
闭式江水源热泵系统水流量最优值的计算方法
A calculation method for the optimal water flow of closed-loop water source heat pump systems (WSHP)at Yangtze River
摘要
Abstract
The water flow of closed-loop heat exchanger coil influences the overall performance of water source heat pump systems(WSHP). Energy consumption model of water source heat pump systems and calculation method of optimal water flow are both established. Through the theoretical calculations of water source heat pump systems performance, the theoretical relationship between overall coefficient of performance(COP)and percentage of cooling water flow and temperature of the water source heat pump systems is gotten. In the given temperature conditions, the value of the system COP is optimal under a percentage of cooling water flow. A closed-loop water source heat pump test bench is established in Yangtze River. Then, the variable flow conditions experiments are both done in summer and winter, experimental results and theoretical results are consistent. The calculation method can provide a reference for further research of the performance of closed-loop water source heat pump systems.关键词
水源热泵/闭式换热器/水流量最优值/性能系数Key words
water source heat pump system/ closed-loop heat exchanger coil/ optimal water flow/ coefficient of performance分类
建筑与水利引用本文复制引用
王勇,卿菁,刘清华..闭式江水源热泵系统水流量最优值的计算方法[J].重庆大学学报,2013,36(3):109-113,134,6.基金项目
国家科技部"十一五"科技攻关项目:水源地源热泵高效应用关键技术研究与示范(2006BAJ01A06) (2006BAJ01A06)