高压电器2013,Vol.49Issue(6):67-71,77,6.
基于等值老化的变压器绝缘寿命损失研究
Research on Insulation Life Loss of Power Transformer Based on Equivalent Aging
摘要
Abstract
During a power transformer's service period,the key factor that influences the insulation life of transformer is the hot-spot temperature.In this paper,statistical models of load factor and ambient temperature,which are the two most important parameters influencing the hot-spot temperature,are established.Moreover,the stochastic behaviors of the load factor and ambient temperature are simulated through the Ornstein-Uhlenbeck process.Based on the equivalent aging model from the IEEE loading guide,annual life losses of transformer insulation under both ideal and practical conditions are analyzed via Monte-Carlo simulation to forecast transformer service life.关键词
电力变压器/热点温度/等值老化/蒙特卡洛法/寿命损失Key words
power transformer/hot-spot temperature/equivalent aging/Monte-Carlo method/life loss分类
信息技术与安全科学引用本文复制引用
黄晓峰,周利军,吴广宁,赵赢峰,杜清全,赵虎..基于等值老化的变压器绝缘寿命损失研究[J].高压电器,2013,49(6):67-71,77,6.基金项目
国家自然科学基金项目(51107105/E0705) (51107105/E0705)
四川省杰出青年基金项目(2011JQ0009) (2011JQ0009)
Project Supported by National Natural Science Foundation of China (51107105/E0705),Outstanding Youth Foundation of Sichuan (2011JQ0009). (51107105/E0705)