高压电器2013,Vol.49Issue(8):96-101,6.
252 kV瓷柱式断路器在AG5条件下的抗震研究
Seismic Research on 252 kV Porcelain Circuit Breaker Under AG5
武胜斌 1金松安 1陈刚 2张文兵 1汪秋宾 2李西育1
作者信息
- 1. 西安高压电器研究院有限责任公司,西安710077
- 2. 中国中铁二院工程集团有限责任公司,成都610031
- 折叠
摘要
Abstract
In order to study the seismic performance of 252 kV porcelain circuit breaker under AG5,the reason for porcelain circuit breaker easy to be broken during earthquake is analyzed.In AG5 conditions,seismic performance of typical 252 kV porcelain circuit breaker has been calculated.The results show that:the natural frequency is increased obviously without chassis,so reasonable frequency could be designed to different geological conditions in order to reduce the damage from the earthquake to the circuit breaker;the highest stresses occurred in the root of the porcelain cylinder for with or without the chassis which exceeded the limit stress of the common porcelain.High strength porcelain insulator may be used in order to increase circuit breaker's anti-seismic performance.But,in very high seismic level region,it is not recommended to use porcelain type circuit breaker,especially in electric railway substation.关键词
瓷柱断路器/抗震性能/固有频率/252 kVKey words
porcelain circuit break/ seismic performance/ natural frequency/ 252 kV分类
信息技术与安全科学引用本文复制引用
武胜斌,金松安,陈刚,张文兵,汪秋宾,李西育..252 kV瓷柱式断路器在AG5条件下的抗震研究[J].高压电器,2013,49(8):96-101,6.