In order to study the seismic performance of 252 kV porcelain circuit breaker under AG5,the reason for porcelain circuit breaker easy to be broken during earthquake is analyzed.In AG5 conditions,seismic performance of typical 252 kV porcelain circuit breaker has been calculated.The results show that:the natural frequency is increased obviously without chassis,so reasonable frequency could be designed to different geological conditions in order to reduce the damage from the earthquake to the circuit breaker;the highest stresses occurred in the root of the porcelain cylinder for with or without the chassis which exceeded the limit stress of the common porcelain.High strength porcelain insulator may be used in order to increase circuit breaker's anti-seismic performance.But,in very high seismic level region,it is not recommended to use porcelain type circuit breaker,especially in electric railway substation.

关键词

瓷柱断路器/抗震性能/固有频率/252 kV

Key words

porcelain circuit break/ seismic performance/ natural frequency/ 252 kV