转轮式两级蒸发冷却空调的运行费用分析
Running Cost Analysis of Rotary Type Two-Stage Evaporative Cooling Air-conditioning
罗绒 1黄翔 1沈柏青 2刘晓峰 2陈本林2
作者信息
- 1. 西安工程大学,陕西西安 710048
- 2. 南通昆仑空调有限公司,江苏南通 226008
- 折叠
摘要
Abstract
In this paper, taking a practical supermarket as an example, in order to budget the supermarket economy of the rotary heat recovery indirect-direct evaporative cooling air conditioning unit, in dry areas of Xinjiang, this is further 210000 m3/h unit illustrated by an example, the refrigerating capacity,energy consumption and the EER compared between the rotary two-stage evaporative cooling air conditioning unit and the traditional mechanical refrigeration air conditioning unit. Satisfying human comfort, calculating running energy consumption of the two units from March to October (3430 hours), and ultimately calculating the operating costs of the rotary heat recovery indirect-direct evaporative cooling air conditioning unit than the traditional mechanical refrigeration air conditioning unit 63 million yuan, effectively reducing the energy consumption of air conditioning system, reducing the running costs of the supermarket.关键词
热回收/蒸发冷却/机械制冷/能效比/运行费用Key words
Heat recovery/Evaporative cooling/Mechanical refrigeration/Energy efficiency/Operating costs引用本文复制引用