高压电器2013,Vol.49Issue(9):86-90,5.
应用电网雷害分布合理布置500 kV线路避雷器
Reasonable Arranging Arresters for 500 kV Transmission Line by Use of Lightning Distribution
杨杰 1郑宇清 1吕晓燕 2赵波1
作者信息
- 1. 冀北电力检修分公司大同分部,大同037006
- 2. 山西电力大同供电分公司,大同037001
- 折叠
摘要
Abstract
It is expensive and wasted that arresters were widely installed for 500 kV transmission line.To solve this problem,a way has been proposed.By lightning distribution,the site survey and theoretical calculations,the shielding failure rate of transmission line is calculated.Then arranging sites of arresters could be chosen in accordance with the values of shielding failure rates.A fine-tuning device of gas gap is designed for the arrester.Arresters with series gaps have been fitted in North China for the first time.It is proved that the improved electrogeometric model is valid.It is reasonable arranging arresters of 500 kV transmission line by this way.关键词
雷害分布/电气几何模型/绕击跳闸率/华北电网/空气间隙避雷器Key words
lighting distribution/ EGM/ shielding failure flashover rate/ North China Grid/ arrester with series gap分类
信息技术与安全科学引用本文复制引用
杨杰,郑宇清,吕晓燕,赵波..应用电网雷害分布合理布置500 kV线路避雷器[J].高压电器,2013,49(9):86-90,5.