电工技术学报Issue(2):260-270,11.
含风电接入的发输电系统风险评估
Risk Assessment of Generation and Transmission Systems Considering Wind Power Penetration
摘要
Abstract
The reliability model of the wind farm is established considering the randomness of the wind speed, the power characteristics of the wind turbine, wind turbine operation conditions, derating operating status, step-up transformer and high-voltage transmission line failure rate and other factors. Because the traditional assessment method has large sample size and low efficiency for large-scale wind power penetration, the new assessment method for generation and transmission systems with large-scale wind power based on scattered sampling monte-carlo technique is proposed in this paper. This method has [0,1] interval divided into several sub-interval in which the system index can be calculated independently which indirectly increase the sampling frequency of the fault condition. So the scattered sampling Monte-Carlo method could reduce sample times and enhance sampling efficiency. According to the random and intermittent of wind power, the risk indexes which fully reflect the impact of power generation and transmission systems are given. The calculation and analysis of improved IEEE-RTS 79 reliability test systems show that the proposed algorithm is effective.关键词
蒙特卡洛仿真/风险评估/发输电系统/分散抽样/风电Key words
Monte-Carlo simulation/risk assessment/power generation and transmission system/scattered sampling technique/wind power分类
信息技术与安全科学引用本文复制引用
蒋程,刘文霞,张建华,俞悦,余加喜,刘德先..含风电接入的发输电系统风险评估[J].电工技术学报,2014,(2):260-270,11.基金项目
国家高技术研究发展计划(863计划)资助项目(2012AA050201)。 ()