空军工程大学学报(自然科学版)Issue(6):59-63,5.DOI:10.3969/j.issn.1009-3516.2013.06.014
避雷针接闪对通信台站布线及接地系统影响分析
Analysis of the Influence of Lightning Rod Current upon the Wiring and the Grounding Systems of Communication Stations
杜思深 1庄绪春 1李伟1
作者信息
- 1. 空军工程大学信息与导航学院,陕西西安,710077
- 折叠
摘要
Abstract
This paper begins with the analysis of the protection range of lightning rod and lightning current, focusing on the discussion of the metal wire frame around the down lead,formed with wires of communica-tion stations and the grounding system.The calculating result shows that the greater the lightning peak value,the shorter the wave front time,the nearer the metal wire frame with the lightning spot and the more likely the electrical device is compromised.If the metal wire frame works as the common ground of the lightning proof,the protection,working circuit,and the ground potential of the common ground fail to be equal everywhere due to the high voltage induction such as lightning with the fluctuations of voltage ranging from hundreds to thousands of volts,undermining electrical devices in the communication stations, especially the disruption of logic integrated circuit,the crash of CPU and hardware damage.The conclu-sion shows that the quantitative analysis of the paper provides a reference basis for the design of the thun-der prevention of communication stations.关键词
雷电/电磁感应/防雷建筑/接地系统Key words
lightning/electromagnetic induction/structures against lightning/grounding system分类
动力与电气工程引用本文复制引用
杜思深,庄绪春,李伟..避雷针接闪对通信台站布线及接地系统影响分析[J].空军工程大学学报(自然科学版),2013,(6):59-63,5.