数据机房冷区内气流组织的优化

沈向阳 陈嘉澍 卓献荣 吕金虎

流体机械Issue(3):71-75,31,6.
流体机械Issue(3):71-75,31,6.DOI:10.3969/j.issn.1005-0329.2014.03.016

数据机房冷区内气流组织的优化

Optimization of Air Distribution in a Data Center’s Cold-zone

沈向阳 1陈嘉澍 2卓献荣 1吕金虎1

作者信息

  • 1. 仲恺农业工程学院,广东广州510225
  • 2. 中山大学,广东广州510006
  • 折叠

摘要

Abstract

The model of air flow for data center’cold-zone has been set up.The velocity distribution of the data center’s cold-zone are simulated by FLUENT simulation software.The simulated values fit well with the measured values.As for the defect of air distribution about cold-zone,an optimized project is given from the server inlet air uniformity,which simulated and analyzed by FLUENT simulation software.The results show that the baffle thickness has little effect to the server inlet air uniformity at cold-zone,the baffle height must be more than the server inlet height.When the distance of static baffle to main air port is 0.40 m,the air flow field at cold-zone is the best.And then the server inlet air quite uniform,which guarantee the effective heat dissi-pation of the server.

关键词

数据机房/冷区/气流组织/模拟/服务器

Key words

data center/cold -zone/air distribution/simulation/server