| 注册
首页|期刊导航|宁夏电力|串级式电压互感器铁磁谐振对介损试验的影响

串级式电压互感器铁磁谐振对介损试验的影响

侯峰

宁夏电力Issue(5):20-22,33,4.
宁夏电力Issue(5):20-22,33,4.DOI:10.3969/j.issn.1672-3643.2013.05.006

串级式电压互感器铁磁谐振对介损试验的影响

The influence of ferro-resonance phenomenon of cascade-type voltage transformer on dielectric loss test

侯峰1

作者信息

  • 1. 国网宁夏电力公司检修公司,宁夏 银川 750011; 西安交通大学高电压技术教研室,陕西 西安 710049
  • 折叠

摘要

Abstract

Aiming at the problem of the test data occur shift when dielectric loss factor measurement of voltage transformer of 220 kVⅠbus bar in Guandi Substation, based on principle of ferro-reso-nance, analyzes the influence of ferro-resonance phenomenon of cascade type voltage transformer on dielectric loss factor measurement, puts forward feasible solution.The application result shows that it is a simple and effective solution using standby dynamo supply voltage source to the test instrument.

关键词

串级式电压互感器/铁磁谐振/介质损耗因数

Key words

cascade-type voltage transformer/ferro-resonance/dielectric loss factor

分类

信息技术与安全科学

引用本文复制引用

侯峰..串级式电压互感器铁磁谐振对介损试验的影响[J].宁夏电力,2013,(5):20-22,33,4.

宁夏电力

1672-3643

访问量0
|
下载量0
段落导航相关论文