水处理设备间冷泵传动轴断裂失效分析

Fracture of Transmission Shaft in the Indirect Cooling Pump for Water Treatment Equipment

王晔星1

作者信息

  • 1. 宝钢股份有限公司能源环保部,上海 200940
  • 折叠

摘要

Abstract

Failure analysis was conducted on the fractured transmission shaft of the indi-rect cooling pump for the 4CC No.1 water treatment facility of Baosteel. Through stress cal-culation and fracture analysis of the shaft and material and mechanical property comparison between the fractured shaft and the newly-replaced shaft, brittleness of the shaft was finally identified as the direct cause of the fracture, while the installation quality and heat treatment process of the equipment were the fundamental reason for the fracture.

关键词

/传动轴/失效分析

Key words

pump/transmission shaft/failure analysis