中国电机工程学报Issue(28):161-167,7.
±1100 kV特高压直流换流阀冲击电压试验能力研究
Study on the Impulse Test Capability of ±1 100 kV UHVDC Converter Valve
摘要
Abstract
In order to meet the requirements of dielectric tests on ±1 100 kV ultra high voltage direct current (UHVDC) converter valve, the impulse test method of ±1 100 kV UHVDC converter valve has been studied. Surface electric field intensity on shielding cases of the impulse test equipment was calculated by using Galerkin boundary element method. According to existing conditions, a feasible measure was proposed, which can be employed to decrease electric field dramatically and avoid corona discharge of shielding cases. In addition, the test circuits for ±1 100 kV converter valve were put forward, and the design for equivalent loads was studied.关键词
±1100 kV/特高压换流阀/冲击电压试验/电场/等效负载Key words
±1100 kV/UHVDC converter valve/impulse voltage test/electric field/equivalent load分类
信息技术与安全科学引用本文复制引用
刘士利,魏晓光,曹均正,查鲲鹏,王高勇,宗文志..±1100 kV特高压直流换流阀冲击电压试验能力研究[J].中国电机工程学报,2013,(28):161-167,7.基金项目
The National High Technology Research and Development of China 863 Program (2012AA052702) (2012AA052702)