中国电机工程学报Issue(4):659-665,7.DOI:10.13334/j.0258-8013.pcsee.2014.04.018
特高压直流输电工程单极保护降压试验研究
Study on Monopole Protective Reduce Voltage Test of ±800 kV UHVDC Transmission Project
杨万开 1印永华 1曾南超1
作者信息
- 1. 中国电力科学研究院,北京市 海淀区 100192
- 折叠
摘要
Abstract
The AC system voltage control strategy was researched based on Xiangjiaba to Shanghai (abbr. XS) ultra high-voltage direct current (UHVDC) rectifier side (Fulong station) weak system during XS UHVDC project system commissioning test, and the countermeasure method prevented to fault for monopole rated power operation test was proposed. The variety procedure of DC voltage, DC current and firing angle and so on were analyzed, the UHVDC control system characteristics, AC side and DC side over voltage were analyzed during monopole rated power protective reduced voltage test. The reactive power and voltage control parameters were proposed and carried out to set temporarily at Fulong station, in order to guarantee AC bus voltage stability and reduced voltage 70%test success during monopole rated power operation test. The validity of system calculation analysis results was verified before XS UHVDC system test by rectifier station reactive power and voltage calculation analysis based on DC parameters measured in the test. The DC voltage and current intense variety in rectifier could not infect the system safety and stability operation by analyzing system voltage stability.关键词
特高压直流输电工程/单极额定功率运行/保护降压试验/无功功率和电压控制Key words
ultra high-voltage direct current (UHVDC) project/monopole rated power operation/protective reduced voltage test/reactive power and voltage control分类
信息技术与安全科学引用本文复制引用