Mechanism Research of High Resistance Grounding for Shipboard Medium Voltage Power Grid

张彦魁 1毕大强 2刘同和1

作者信息

  • 1. 电力系统国家重点实验室,北京100084
  • 2. 清华大学电机系,北京100084
  • 折叠

摘要

Abstract

When High Resistance Grounding(HRG)is used for shipboard Medium Voltage(MV)power grid,the mechanisms and laws can be quite complicated,which so far lacks quantitative research. Based on the theoretical analysis of single-phase ground fault for shipboard MV power grid,and taking a stand-alone system with diesel engine and excitation voltage control as example,this paper studies the HRG in detail combined with Simulink transient simulation. The research mainly focuses on the impact of impedance ratio of HRG on arc-extinct recovery voltage,re-strike overvoltage,neutral displacement volt-age,and fault current. In addition,the effects of generator frequency offset,arc angle,and fault transition re-sistance are also discussed. The results show that with the increase of impedance ratio,the longer the time of arc-extinct recovery voltage is,and the higher the peak of arc-extinct recovery voltage,the more seri-ous the re-strike overvoltage is. Increasing the impedance ratio could decrease the fault current,but the degree will slow down gradually. The generator frequency offsets can lead to greater transient overvoltage, while the arcing time angle has little impact on the fault current. At last,the general principle of HRG con-figuration is given.

关键词

船舶中压电网/高阻接地/熄弧恢复电压/重燃过电压/故障电流

Key words

shipboard medium voltage power grid/High Resistance Grounding(HRG)/arc-extinct re-covery voltage/re-strike overvoltage/fault current

分类

交通工程

引用本文复制引用

张彦魁,毕大强,刘同和..船舶中压电网高阻接地方式机理研究[J].中国舰船研究,2014,(2):89-94,116,7.

中国舰船研究

OA北大核心CSCDCSTPCD

1673-3185

访问量0
|
下载量0
段落导航相关论文