Abstract

Aiming at the frequent failure of GW7-252 disconnecting switch in switching to the designated po-sition, the device is disassembled and the reasons are detected. It is detected that the major causes are unrea-sonable static contact structure, inferior materials of components and poor strength of drive link and so forth. Moreover, the conduction parts and drive parts are reconstructed for perfection. The practical operation after reconstruction shows that operation of the equipment becomes stable and the potential faults are thoroughly e-liminated.

关键词

GW7/隔离开关/故障分析/完善化改造

Key words

GW7/disconnecting switch/fault analysis/sophistication reconstruction