浙江电力Issue(3):5-9,5.
10kV交联聚乙烯电缆接头缺陷局部放电特性的研究
Research on Partial Discharge Characteristic of 10 kV XLPE Cable Joint Fault
应高亮 1张波 1卢晓峰 1钟伟 1李文斐 2徐志斌2
作者信息
- 1. 国网浙江省电力公司金华供电公司,浙江 金华 321000
- 2. 厦门红相电力设备股份有限公司,福建 厦门 361001
- 折叠
摘要
Abstract
In consideration of the common insulation faults of 10 kV XLPE cable , five typical physical mod-els of intermediate joint insulation faults are made in the laboratory. Through high frequency current method, partial discharge data in different insulation fault models are obtained to form typical partial discharge dia-grams. The test indicates that high frequency current method is feasible and effective to test partial discharge of 10 kV XLPE cables.关键词
XLPE/电缆接头/高频电流法/局部放电Key words
XLPE/cable joint/high frequency current method/partial discharge分类
信息技术与安全科学引用本文复制引用
应高亮,张波,卢晓峰,钟伟,李文斐,徐志斌..10kV交联聚乙烯电缆接头缺陷局部放电特性的研究[J].浙江电力,2014,(3):5-9,5.