输电线路杆塔树根桩基础受外荷载影响的分析
Analysis of Effect of External load on Root Pile Foundations of Transmission Poles and Towers
钟维军1
作者信息
- 1. 宁波市电力设计院有限公司,浙江 宁波 315021
- 折叠
摘要
Abstract
Root pile foundations of overhead transmission lines are applicable for soft soil ground and covers small area. By finite element, design reasonableness of root pile foundation in soft soil and its ability to bear external load are analyzed. The finite element analysis is respectively conducted on external load of places 1 m, 5 m and 8 m away from the bearing platform, from which the displacement and stress are concluded. It is indicated through comparison and analysis on technical parameters that the design of root pile is reasonable and the pile of dirt within 8m from the bearing platform have great impact on root pile foundation. Therefore , the external load should be taken into consideration during the design. The pile of dirt 8 m away from the bearing platform has little impact on root pile foundation, and therefore some structural measures can be adopted to meet the design requirement.关键词
输电线路/杆塔/软土地基/树根桩/基础Key words
transmission lines/poles and towers/soft soil foundation/root pile foundation/base分类
建筑与水利引用本文复制引用
钟维军..输电线路杆塔树根桩基础受外荷载影响的分析[J].浙江电力,2014,(3):17-20,45,5.