重庆大学学报Issue(3):8-14,7.DOI:10.11835/j.issn.1000-582X.2015.03.002
室内环境参数对室外气象参数瞬时变化的动态响应研究
Dynamic response study of the indoor environmental parameters for variable outdoor meteorological conditions
摘要
Abstract
To study the indoor environment parameters dynamic response to the instantaneous variation of outdoor meteorological conditions in Lanzhou,a standard k-ε turbulent model of CFD is adopted to numerically analyze the pollutant concentration field and airflow distribution in an office when the unsteady heat transfer through outer walls is considered.The velocity field,temperature field and pollutant concentration field of two air supply modes,ceiling air supply and lateral air supply,are obtained.The results indicate that the pollutant concentration field and migration characteristics are affected significantly by the solar radiation resulting from stimulating the natural convention heat transfer in the room.Under the same air supply mode,the indoor pollutant concentration is more uniform at 16:00 than that at 8:00.And the average value of pollutant concentration at 8:00 is relatively higher than that at 16:00.At the same air supply parameters,the ceiling air supply mode is more beneficial to lower the indoor pollutant concentration.关键词
室外气象条件/非稳定传热/通风模式/气流组织/空气品质Key words
outdoor meteorological condition/unsteady heat transfer/ventilation mode/airflow organization/air quality分类
建筑与水利引用本文复制引用
王烨,张文霞,胡文婷..室内环境参数对室外气象参数瞬时变化的动态响应研究[J].重庆大学学报,2015,(3):8-14,7.基金项目
国家自然科学基金项目(51266004,51476073);甘肃省自然科学基金项目(1308RJZA151)。Supported by National Natural Science Foundation of China (51266004,51476073)and Natural Science Foundation of Gansu Province(1308RJZA151). ()