电力系统自动化Issue(11):193-198,207,7.DOI:10.7500/AEPS20140416010
110 kV 电阻接地系统电气设备适应性研究及试验
Research on Adaptability of Electrical Equipment of 110 kV Resistance Grounding System and Experiment
摘要
Abstract
1 10 kV neutral resistance grounding system is able to eliminate voltage sag on the load side due to the single-phase grounding fault.At the same time,however,the voltage of the neutral point and non-fault phase voltage to ground will be elevated.So part of the 1 10 kV electrical equipment used in the original neutral direct grounding system cannot be used directly in the 1 10 kV neutral resistance grounding system.The adaptability of electrical equipment for the 1 10 kV neutral resistance grounding system is studied through theoretical analysis and simulation.Suggestions are made for selection of 1 10 kV electrical equipments.And a field experiment on the 1 10 kV neutral resistance grounding system is performed to prove the feasibility and excellence of 1 10 kV neutral resistance grounding system. This work is supported by State Grid Hubei Electric Power Company(No.521 5B014003 H).关键词
中性点经电阻接地/电气设备/适应性/现场试验/电能质量/电压暂降Key words
neutral resistance grounding system/electrical equipment/adaptability/experimental research/power quality/voltage sag引用本文复制引用