| 注册
首页|期刊导航|辽宁石油化工大学学报|室内燃气报警器的安装位置优化

室内燃气报警器的安装位置优化

王鹤超 吴明 程猛猛 杨蕊 谢飞 万书斌

辽宁石油化工大学学报Issue(6):42-46,5.
辽宁石油化工大学学报Issue(6):42-46,5.DOI:10.3696/j.issn.1672-6952.2014.06.009

室内燃气报警器的安装位置优化

Optimization of the Installation Positions of the Indoor Gas Alarms

王鹤超 1吴明 1程猛猛 1杨蕊 1谢飞 1万书斌2

作者信息

  • 1. 辽宁石油化工大学石油天然气工程学院,辽宁抚顺 113001
  • 2. 中石化胜利油建工程有限公司,山东东营 257000
  • 折叠

摘要

Abstract

Gas belongs to flammable and explosive hazardous gas.When the leakage of gas occurred in limited indoor space, the serious consequences would be produced.According to the characteristics of the gas leakage diffusion,firstly Gambit was established indoor gas stove nozzle dispersion physical model.Secondly CFD fluid dynamics software FLUENT was used to simulate the diffusion process of continuous leakage.Finally comparing the diffusion results under certain temperature gradient but different moisture conditions,and monitoring the specified installation area with variety of mounting points,the aim was to optimize the installation position of the alarm.The results show that the location of distance and relative humidity of indoor air were both the key factors on affecting the alarm time.For the same mounting points,relative air humidity increasing 1 5%would cause delaying the time of alarm nearly 6 s;under the same air relative humidity,each time the alarm was away from the leaking mouth increasing by 1 metre,alarm time would lag for 4 s.

关键词

泄漏扩散/相对湿度/安装位置/燃气报警器/优化

Key words

Leakage diffusion/Relative humidity/Installation position/Gas alarm/Optimization

分类

能源科技

引用本文复制引用

王鹤超,吴明,程猛猛,杨蕊,谢飞,万书斌..室内燃气报警器的安装位置优化[J].辽宁石油化工大学学报,2014,(6):42-46,5.

辽宁石油化工大学学报

1672-6952

访问量0
|
下载量0
段落导航相关论文