广东电力Issue(7):116-120,5.DOI:10.3969/j.issn.1007-290X.2014.07.024
220 kV变电站GIS断路器短路典型事故分析
Analysis on Typical GIS Breaker Short-circuit Fault in 220 kV Substation
李晓刚1
作者信息
- 1. 广州粤能电力科技开发有限公司,广东 广州 510080
- 折叠
摘要
Abstract
This paper introduces one GIS breaker short-circuit accident in some 220 kV substation.By comprehensively analy-zing fault recording,gas components,breaker disintegration and factory original data after the short-circuit fault,the main reason for the accident was considered to be defect of breaker interelectrode insulating cylinder caused by breakdown and discharge in factory lightning impulse test.Meanwhile,by review on the accident,correctness of accident reason analysis was verified from another angle and relevant suggestions were proposed for providing references on similar GIS fault handling a-nalysis.关键词
气体绝缘金属封闭开关设备/短路故障/绝缘/缺陷Key words
gas insulated metal enclose switchgear/short-circuit fault/insulation/defect分类
信息技术与安全科学引用本文复制引用
李晓刚..220 kV变电站GIS断路器短路典型事故分析[J].广东电力,2014,(7):116-120,5.