GIS局部放电特高频时差定位法应用案例分析
Analysis on Application Case of GIS Partial Discharge Ultra-high Frequency Time-of-arrival Location
尤德锋 1李兴旺 2庞小峰2
作者信息
- 1. 广州粤能电力科技开发有限公司,广东 广州 510080
- 2. 广东电网公司电力科学研究院,广东 广州 510080
- 折叠
摘要
Abstract
Partial discharge detection is a key technological means for gas insulated switchgear state diagnosis at present. This paper analyzes various partial discharge detection methods and considers that ultra-high frequency is provide with stronger anti-jamming capability and higher detection efficiency which may realize fault mode recognition and positioning. On the ba-sis of the above analysis,one GIS typical suspended discharge defect was discovered by applying partial discharge ultra-high frequency detection method. Afterwards,ultra-high frequency time-of-arrival location was used to ensure defect position and phase synchronous technology was used to confirm defect phase. By strip inspection,the result was verified agreed with diagnosis result of ultra-high frequency method.关键词
局部放电/特高频时差定位法/悬浮放电Key words
gas insulated switchgear/partial discharge/ultra-high frequency time-of-arrival location/suspended discharge分类
信息技术与安全科学引用本文复制引用
尤德锋,李兴旺,庞小峰..GIS局部放电特高频时差定位法应用案例分析[J].广东电力,2014,(8):98-101,4.