| 注册
首页|期刊导航|广东电力|500 kV GIS断路器内置特高频传感器灵敏度校验方法

500 kV GIS断路器内置特高频传感器灵敏度校验方法

庞小峰 李兴旺 吕鸿 王增彬 吴建明 黎量 刘昌标 郑书生

广东电力Issue(10):112-115,4.
广东电力Issue(10):112-115,4.DOI:10.3969/j.issn.1007-290X.2014.10.022

500 kV GIS断路器内置特高频传感器灵敏度校验方法

Verification Method for Sensitivity of Built-in Ultra-high Frequency Sensor in 500 kV GIS Breaker

庞小峰 1李兴旺 1吕鸿 1王增彬 1吴建明 2黎量 3刘昌标 3郑书生3

作者信息

  • 1. 广东电网有限责任公司电力科学研究院,广东 广州 510080
  • 2. 珠海市伊特高科技有限公司,广东 珠海 519060
  • 3. 高电压与电磁兼容北京市重点实验室 华北电力大学,北京 102206
  • 折叠

摘要

Abstract

In practical operation,partial ultra-high frequency sensor is easy to be damaged for reasons of impact by vibration, temperature,humidity,internal and external shock signals and so on.It is playing very important role in ensuring safe and reliable operation of equipments by scientifically and effectively verifying sensitivities of running sensor and detection sys-tem.But present conventional methods are not suitable for on-site verification.Therefore,a method based on equivalent in-jection of field intensity was used to realize on-site verification and experimental testing on built-in ultra-high frequency sen-sor in some 500 kV gas insulated metal enclosed switchgear was conducted.Testing results indicated that this sensor was able to detect 1 pC discharge,equivalent injection of field intensity was feasible for on-site verification and frequency spectrum of injected signals were similar with partial discharge frequency spectrum.

关键词

气体绝缘金属封闭开关设备/局部放电/特高频/内置传感器/灵敏度校验

Key words

gas insulated metal enclosed switchgear/partial discharge/ultra-high frequency/built-in sensor/sensitivity verification

分类

信息技术与安全科学

引用本文复制引用

庞小峰,李兴旺,吕鸿,王增彬,吴建明,黎量,刘昌标,郑书生..500 kV GIS断路器内置特高频传感器灵敏度校验方法[J].广东电力,2014,(10):112-115,4.

广东电力

OACSTPCD

1007-290X

访问量0
|
下载量0
段落导航相关论文