摘要
Abstract
A deliberated study finds that the cause for feeder frequent tripping in a 10kV substation is the unreasonable parameter settings of series reactors in shunt capacitor banks of reactive power compensation device. Thus high harmonic currents in shunt capacitors are amplified by the effect of non-linear loads power system which results in the break tripping. The paper further proposes practical resolutions to the problems.关键词
并联电容器/谐波放大/串联电抗器/断路器跳闸Key words
shunt capacitors/harmonic currents amplification/series reactors/break tripping分类