流体机械Issue(4):67-71,22,6.DOI:10.3969/j.issn.1005-0329.2014.04.014
交叉式露点间接蒸发冷却空调机组应用于模拟机房的试验研究
Experimental Study in the Simulation Data Center of Cross Dew Point Indirect Evaporative Cooling Air Conditioning Unit
宋姣姣 1黄翔 1范坤 1黄华铃 2陈明松2
作者信息
- 1. 西安工程大学,陕西西安710048
- 2. 澳蓝 福建 实业有限公司,福建福州350000
- 折叠
摘要
Abstract
In order to meet environmental requirements of electronic equipment and facilities,the cross dew point indirect evap-orative cooling air conditioning unit is developed.July 5 -15,2013 in fuzhou,fujian,the cross dew point indirect evaporative cooling air conditioning unit test in simulation data center.1kW and 2kW only opening heat source and opening heat source at the same time opening the unit measure the method of comparison respectively.Two cases measure temperature and humidity distribu-tion of equipment.The contrast analysis:opening the unit under the optimum air volume ratio,2kW heat source surface tempera-ture drop is 8.9 ℃,basically ASHRAETC 9.9 released the largest temperature and humidity of equipment drop 2.3 ℃,it meet 2、3 level of the environmental requirements;opening the unit Under the worst air volume ratio,1 kW heat source shows that the maximum temperature drop is 2.3 ℃,the temperature and humidity of equipment meet 1 ~4 level of the electronic requirement.关键词
模拟机房/机房环境要求/交叉式露点间接/蒸发冷却Key words
simulation data center/equipment environmental requirements/cross dew point indirect/evaporative cooling分类
机械制造引用本文复制引用
宋姣姣,黄翔,范坤,黄华铃,陈明松..交叉式露点间接蒸发冷却空调机组应用于模拟机房的试验研究[J].流体机械,2014,(4):67-71,22,6.