流体机械Issue(9):57-60,4.DOI:10.3969/j.issn.1005-0329.2014.09.013
热水型溴化锂制冷机喷淋式发生器性能试验研究
Experimental Research on Spray Type Generator of LiBr Refrigerator driven by hot Water
摘要
Abstract
Effects of LiBr solution spray density and solution concentration on heat and mass transfer in spray type generator is researched by the experimental analysis. The experimental results show that,while the solution spray density increases,the heat transfer coefficient of solution increases in the outside surface of spray generator,the amount of steam increases until it reaches maximum,then decreases,and heat transfer coefficient decreases with increasing concentration of LiBr solution,when the concen-tration is less than 50% for the linear relationship between the two,when the concentration is greater than 50% for the nonlinear relationship between the two.关键词
传热系数/喷淋发生器/传热传质/溴化锂制冷机Key words
heat transfer coefficient/spray type generator/heat and mass transfer/LiBr refrigerator分类
机械制造引用本文复制引用
姚远,陆振能,骆超,龚宇烈,王显龙,廉永旺..热水型溴化锂制冷机喷淋式发生器性能试验研究[J].流体机械,2014,(9):57-60,4.基金项目
国家科技支撑计划项目(2012BAB12B01) (2012BAB12B01)
广州市产学研合作项目(2013Y2-00091) (2013Y2-00091)