流体机械Issue(3):52-57,6.DOI:10.3969/j.issn.1005-0329.2015.03.011
干燥工况下新型复合式露点间接蒸发冷却空调机组的试验研究
Experimental Study of a Novel Combined Dew Point Indirect Evaporative Air Conditioning Unit under Dry Condition
摘要
Abstract
A range of drying conditions:29 ~35 ℃ dry bulb temperature and 18 ~23 ℃ wet bulb temperature has been simula-ted in Fuzhou experimental base from January 6 to 18.By means of a novel combined dew point indirect evaporative air condition-ing unit tests,the results showed that the best secondary to primary air ratio is 0.72,the best spary water quantity is 450 L/h,the wet-bulb efficiency of 22.5℃ circulating water temperature is 115% and the wet-bulb efficiency of the 16℃ tap-water tempera-ture is 121%.Units in the best condition to run 30 minutes consumes 2.62L of water.关键词
蒸发冷却/露点间接/干燥工况/性能参数Key words
evaporative cooling/dew point Indirect/dry condition/performance parameter分类
机械制造引用本文复制引用
刘佳莉,黄翔,韩正林,黄华铃..干燥工况下新型复合式露点间接蒸发冷却空调机组的试验研究[J].流体机械,2015,(3):52-57,6.基金项目
西部地区利用干空气可再生能源的节能低碳型蒸发冷却空调开发与应用(2011KTCQ01-10);陕西省科技统筹创新工程计划项目 ()