南方电网技术Issue(4):42-46,5.DOI:10.13648/j.cnki.issn1674-0629.2014.04.008
基于实际录波的南方电网多回直流换相失败分析
Analysis on Commutation Failure of the CSG’s HVDC Systems Based on Actual Waves
赵利刚 1赵勇 1洪潮 1徐光虎 2林庆标 2张帆1
作者信息
- 1. 南方电网科学研究院,广州 510080
- 2. 中国南方电网电力调度控制中心,广州 510623
- 折叠
摘要
Abstract
Commutation failure is one of the very frequent dynamic events in HVDC transmission systems. Most of the commutation failures are caused by the voltage disturbances of AC grid. Aiming at several commutation failure events occurred in China Southern Power Grid (CSG), April to August 2012, and based on the TFR and PMU waves of DC inverter station, and analyzing the changes of AC bus voltage and active power of DC lines during the events, this paper obtains the relevant laws of commutation failure in CSG’s HVDC systems, and proposes a practical criterion for commutation failure occurred in electromechanical transient simulation based on lower voltage sag. According to the criterion, the impact of the line faults occurred in the 50 substations of 500 kV in Guangdong on the DC commutation failure and system stability is evaluated.关键词
高压直流输电/换相失败/实际录波/实用判据Key words
HVDC/commutation failure/actual waves/practical criteria分类
信息技术与安全科学引用本文复制引用
赵利刚,赵勇,洪潮,徐光虎,林庆标,张帆..基于实际录波的南方电网多回直流换相失败分析[J].南方电网技术,2014,(4):42-46,5.