Abstract

During the automatic adjustment of AVC system, the reactive power output of certain power units involved in regulating processis was clearly insufficient, thus the system voltage couldn't reach the given operation limits, and it stayed quite high under load valley. Thus took investigate AVC systems of several power plants in Inner Mongolia to get the main causes for the insufficiency of reactive power output, which was the incorrect setting value, the unit's owned defects, the unreasonable system network structure. And put forward suggestion to set the reasonable setting value to make the units participate the regulating for a greater degree.

关键词

AVC系统/无功功率调节/系统电压/定值设置

Key words

AVC system/reactive power regulation/system voltage/setting value