智能变电站3/2接线方式中电流互感器配置分析
Configuration analysis of current transformer in 3/2 connection mode of smart substation
庞亚云 1董琪2
作者信息
- 1. 宁夏电力设计院,宁夏 银川 750001
- 2. 国网宁夏电力公司电力科学研究院,宁夏 银川 750011
- 折叠
摘要
Abstract
Aiming at the problem of protection blind area existing in configuration schemes of current transformer of 330 kV substation in general design,by analyzing the characteristics of current transformer,puts forward improvement measures such as to increase number of current transformer winding,adopt TPY level current transformer for the main transformer protection in one and a half circuit breaker connection (3/2 connection) mode, etc. The result shows that the improvement measures can effectively prevent the accident scope spreading,guarantee the power grid safe and reliable operation,reduce economic loss of power grid enterprises and customers.关键词
智能变电站/1个半断路器接线/3/2接线/电流互感器/保护死区Key words
smart substation/one and a half circuit breaker connection/3/2 connection/current transformer,protection blind area分类