天津科技大学学报Issue(2):60-64,5.DOI:10.13364/j.issn.1672-6510.20140100
喷嘴及其布置方式对冷却塔性能的影响
Influence of Nozzle Type and Arrangement on the Performance of Cooling Tower
闵健 1王连声 1姜媛媛 1郭丽慧 1腾东玉 1赵虎军1
作者信息
- 1. 国电龙源电力技术工程有限责任公司,北京 100039
- 折叠
摘要
Abstract
Based on the spray performance experiments of XPH and TP-Ⅱ nozzles,the water distribution throughout the whole tower affected by different parameters and arrangement of nozzles was analyzed. The results show that the flow coef-ficient of XPH is low and able to apply to the condition where pressure head is larger than 10,kPa. Groups of TP-Ⅱ nozzles should be used to make water well distributed. XPH nozzles should be positioned as an equilateral triangle at the wall zone in the tower. The middle zone full of air should be controlled by TP-Ⅱ nozzles arranged as a square. TP-Ⅱ nozzles distributed as a regular hexagon should be used at the core of the tower to reduce the spraying consistency and investment. The results can provide quantitative references for the optimization of cooling design and transformation.关键词
冷却塔/流量系数/喷溅半径/淋水不均匀性系数Key words
cooling tower/flow coefficient/splash radius/sprinkling non-uniformity coefficient分类
能源科技引用本文复制引用
闵健,王连声,姜媛媛,郭丽慧,腾东玉,赵虎军..喷嘴及其布置方式对冷却塔性能的影响[J].天津科技大学学报,2015,(2):60-64,5.