| 注册
首页|期刊导航|原子能科学技术|AP1000多根蒸汽发生器传热管破裂分析

AP1000多根蒸汽发生器传热管破裂分析

叶杰 蔡伟 陈文虎

原子能科学技术Issue(6):1057-1061,5.
原子能科学技术Issue(6):1057-1061,5.DOI:10.7538/yzk.2015.49.06.1057

AP1000多根蒸汽发生器传热管破裂分析

Analysis of Multiple Steam Generator Tube Rupture for AP 1000

叶杰 1蔡伟 1陈文虎1

作者信息

  • 1. 深圳中广核工程设计有限公司 上海分公司,上海 200241
  • 折叠

摘要

Abstract

The multiple steam generator tube rupture accident in AP1000 was analyzed using RELAP5/MOD3 code .Based on best‐estimated method ,1‐5 steam generator tube rupture cases were analyzed . The results show that the main steam safety valve (MSSV) remains closed with power‐operated relief valves available and the containment bypass will not occur .In each case ,there is no core makeup tank level reduction and no automatic depressurization signal generated .Even if MSSV is postulated to stick open , the core is never uncovered and remains cooled .

关键词

A P1000/REL A P5/M OD3/多根蒸汽发生器传热管破裂/蒸汽发生器

Key words

AP1000/RELAP5/MOD3/multiple steam generator tube rupture/steam generator

分类

能源科技

引用本文复制引用

叶杰,蔡伟,陈文虎..AP1000多根蒸汽发生器传热管破裂分析[J].原子能科学技术,2015,(6):1057-1061,5.

原子能科学技术

OA北大核心CSCDCSTPCD

1000-6931

访问量3
|
下载量0
段落导航相关论文