| 注册
首页|期刊导航|中国电机工程学报|基于扰动功率的电压暂降源方向判断

基于扰动功率的电压暂降源方向判断

唐轶 文雷 于琪 方永丽 陈奎

中国电机工程学报Issue(9):2202-2208,7.
中国电机工程学报Issue(9):2202-2208,7.DOI:10.13334/j.0258-8013.pcsee.2015.09.013

基于扰动功率的电压暂降源方向判断

A Direction Finder for Voltage Sag Source Based on the Disturbance Power Direction

唐轶 1文雷 1于琪 1方永丽 1陈奎1

作者信息

  • 1. 中国矿业大学信息与电气工程学院,江苏省徐州市 221008
  • 折叠

摘要

Abstract

Voltage sag source location is to determine the disturbance origins’ relative position of monitoring device. By analyzing power system faults, which is the main reason resulting in the voltage sags, the direction of the disturbance power has been found to be a good indicator of the sag source location. If the disturbance power measured at the monitoring point is positive, a disturbance origin is located at upstream, and if the disturbance power measured at the monitoring point is negative, a disturbance source is located at downstream. The calculation methods of the disturbance power are presented respectively. The simulation tests show that the proposed method has a high effectiveness in voltage sag source location caused by all kinds of faults. The new method is suitable for any power grid structure (radial type, ring type, one-source, multi-source, etc.), and can also be used in locating other disturbance sources (E.g.: large motor starting, capacitor switching etc.).

关键词

电能质量/电压暂降/源定位

Key words

power quality/voltage sag/source location

分类

信息技术与安全科学

引用本文复制引用

唐轶,文雷,于琪,方永丽,陈奎..基于扰动功率的电压暂降源方向判断[J].中国电机工程学报,2015,(9):2202-2208,7.