浙江电力Issue(8):1-3,3.
自然积污绝缘子污闪电压变异系数的统计分析
Statistical Analysis on Variation Coefficient of Flashover Voltage of Naturally Contaminated Insulators
摘要
Abstract
This paper performs a statistical analysis on distribution rules of variation coefficient of flashover voltage of naturally contaminated insulators obtained by average set-up method and comparatively analyzes the distribution rules and those of variation coefficient of artificial contamination flashover voltage. The results show that the upper confidence limits of variation coefficient of natural pollution flashover voltages , which are obtained with the average step-up method, have a maximum of 0.3101, and the variation coefficients approx-imately comply with normal distribution , with the expectation value of 7.45%, and its upper limit is 8.14%in 95% confidence interval, which is almost consistent with the results obtained with up-and-down method. In general, the dispersity of natural contamination flashover voltage is greater than that of artificial contamina-tion flashover voltage.关键词
绝缘子/自然污秽/污闪电压/变异系数/分散性Key words
insulator/natural contamination/pollution flashover voltage/variation coefficient/dispersity分类
信息技术与安全科学引用本文复制引用
吴明祥,刘江明,王少华,崔竹叶,张杰,许杨勇..自然积污绝缘子污闪电压变异系数的统计分析[J].浙江电力,2014,(8):1-3,3.基金项目
浙江省电力公司重点科技项目 ()