浙江电力Issue(9):6-9,4.
通过保护动作电流定位1000 kV GIS故障点的实例分析
Case analysis on Fault Location of 1 000 kV GIS by Protection Trip Current
赵晓明 1余志慧2
作者信息
- 1. 华北电力大学,北京 102206
- 2. 国网浙江省电力公司电力科学研究院,杭州 310014
- 折叠
摘要
Abstract
A single-phase ground fault of 1 000 kV busbar GIS in an UHV AC substation occurred due to in-sulation. The fault point is hard to detect. The paper comprehensively analyzes protection action of busbar in case of the fault by protection action report and fault recording; By means of distribution magnitude of short-circuit current and its direction during the fault occurred, it suggests the detection area, narrowing the area of fault detection and providing strong technical support to fast detection of fault point.关键词
1 000 kV/变电站/母差保护/短路电流/GIS/故障点Key words
1 000 kV/substation/bus differential protection/short-circuit current/GIS/fault point分类
信息技术与安全科学引用本文复制引用
赵晓明,余志慧..通过保护动作电流定位1000 kV GIS故障点的实例分析[J].浙江电力,2014,(9):6-9,4.