浙江电力Issue(10):1-5,5.
直流偏磁对中性点接地变压器衍生影响的检测分析
Analysis on Derivative Influence Detection of DC Magnetic Bias on Neutral-grounded Transformers
何文林 1孙翔 1邹国平 1张建平1
作者信息
- 1. 国网浙江省电力公司电力科学研究院,杭州 310014
- 折叠
摘要
Abstract
Solar magnetic storm, monopole or asymmetric operation of DC transmission may cause DC mag-netic bias. The actual test indicates that the monopole operation mode of DC transmission causes severe DC bias in neutral-grounded transformers near ground electrodes and DC magnetic bias exerts derivative influence on transformers such as increase of noise, aggravation of vibration and abnormal harmonic and so on.关键词
直流偏磁/变压器/噪声/振动/谐波Key words
DC magnetic bias/transformer/noise/vibration/harmonic分类
信息技术与安全科学引用本文复制引用
何文林,孙翔,邹国平,张建平..直流偏磁对中性点接地变压器衍生影响的检测分析[J].浙江电力,2014,(10):1-5,5.