浙江电力Issue(4):11-14,4.
基于特高频法的1100 kV GIS局部放电故障定位研究
Research on 1 100 kV GIS Partial Discharge Fault Location Based on UHF Technology
王文浩 1胡锡幸 2郦于杰 3何文林 1徐华 1刘江明3
作者信息
- 1. 国网浙江省电力公司电力科学研究院,杭州 310014
- 2. 国网浙江省电力公司杭州供电公司,杭州 310009
- 3. 国网浙江省电力公司检修分公司,杭州 311232
- 折叠
摘要
Abstract
The case that built-in type UHF sensor alarmed after 1 100 kV GIS circuit breaker switching is presented. The fault is located successfully based on the propagation characteristics and pattern recognition techniques of UHF signals, and then attenuation rule of UHF signals in different gas chambers is concluded. By tracking and analyzing the UHF signal amplitude and on-line frequency spectrogram information and de-tecting discharge point by faulty gas chamber disassembly, the above-mentioned diagnosis and analysis is proved correct, providing an effective example for application of UHF-based method in UHV GIS projects. In the final, the paper brings forward some suggestions on field detection of UHF-based method.关键词
特高压/局部放电/特高频法/衰减特性/典型谱图/定位技术Key words
UHV/partial discharge/UHF/attenuation characteristics/typical spectrogram/location tech-nology分类
信息技术与安全科学引用本文复制引用
王文浩,胡锡幸,郦于杰,何文林,徐华,刘江明..基于特高频法的1100 kV GIS局部放电故障定位研究[J].浙江电力,2015,(4):11-14,4.