首页|期刊导航|制冷技术|多联机室内机电子膨胀阀制冷剂内泄漏对制冷综合性能系数的影响

多联机室内机电子膨胀阀制冷剂内泄漏对制冷综合性能系数的影响OA

Effect of the Refrigerant Internal Leakage of Electronic Expansion Valve in Indoor Unit for Multi-split Air Conditioners on Integrated Part Load Value

中文摘要英文摘要

本文研究了多联机室内机电子膨胀阀(EEV)内泄漏对制冷综合部分负荷性能系数(IPLV)的影响。本文进行了两组实验研究,研究结果表明:第一组实验时,有一台室内机膨胀阀始终存在内泄漏,最终 IPLV为4.53;第二组实验时,关闭的内机膨胀阀没有明显内泄漏,最终 IPLV为4.72,比第一组数据提高了4.2%。从实验结果看出,部分负荷下不开机的室内机膨胀阀存在内泄漏,会导致测试的部分负荷制冷量下降,最终导致多联机 IPLV 降低。因此在进行多联机 IP…查看全部>>

The effect of internal leakage of electronic expansion valve (EEV) in indoor unit forMulti-split air conditioners on integrated part load value (IPLV) is studied in the paper. Two groups of experimental investigation were performed. The experimental result shows that, the cooling IPLV of one group is 4.53 when one shut-down indoor unit has the problem of internal leakage under part load condition; the cooling IPLV of other group is 4.72 when all indoor unit …查看全部>>

郁夏夏;路阳;夏晨光;潘国洪;刘从

英格索兰亚太工程技术中心,江苏太仓 215400英格索兰亚太工程技术中心,江苏太仓 215400英格索兰亚太工程技术中心,江苏太仓 215400英格索兰亚太工程技术中心,江苏太仓 215400英格索兰亚太工程技术中心,江苏太仓 215400

多联机制冷综合性能系数电子膨胀阀内泄漏

Multi-split air conditionersIntegrated Part Load ValueElectronic expansion valveInternal leakage

《制冷技术》 2015 (1)

70-73,4

10.3969/j.issn.2095-4468.2015.01.207