| 注册
首页|期刊导航|制冷学报|部分负荷下热湿分段处理空调系统性能实验研究

部分负荷下热湿分段处理空调系统性能实验研究

姜小伟 梁彩华

制冷学报Issue(5):25-29,48,6.
制冷学报Issue(5):25-29,48,6.DOI:10�3969/j�issn�0253-4339�2014�05�025

部分负荷下热湿分段处理空调系统性能实验研究

Experimental Study on Performance of Segmented Handling Air-conditioning System under Part Load Conditions

姜小伟 1梁彩华1

作者信息

  • 1. 东南大学能源与环境学院 南京 210096
  • 折叠

摘要

Abstract

Air conditioning systems are usually operated under part load conditions, and segmented handling air-conditioning system has significant advantages of realizing energy-saving operation under part load conditions. Chillers in serial configuration was carried out on a test bed of segmented handling air-conditioning system, and the performance of system in different load conditions were studied. Experi-ment results show that:the maximum load that segmented handling air-conditioning system can handle is only 81. 5% compared with con-ventional systems when the design load is the same. When the load reduces from 81. 5% to 50%, the chillers of the system average COP increases from 3. 13 to 4. 16, which indicates that segmented handling air conditioning system can create a big energy saving potential un-der part load conditions.

关键词

空调系统/热湿分段处理/部分负荷/节能

Key words

air-conditioning/segmented treatment/part load/energy-saving

分类

建筑与水利

引用本文复制引用

姜小伟,梁彩华..部分负荷下热湿分段处理空调系统性能实验研究[J].制冷学报,2014,(5):25-29,48,6.

制冷学报

OA北大核心CSCDCSTPCD

0253-4339

访问量0
|
下载量0
段落导航相关论文