制冷学报Issue(5):30-37,8.DOI:10�3969/j�issn�0253-4339�2014�05�030
考虑回流的横流冷却塔热力学模型及运行特性分析
Thermodynamic Model and Operating Characteristics of Cross Cooling Tower with Recirculated Air
马建荣 1罗文海 2夏少丹 1蔡博达 1吴疆 1罗定鑫 1冯腾飞 1陈星龙 2刘金平 2刘雪峰2
作者信息
- 1. 广州市地下铁道总公司 广州 510010
- 2. 华南理工大学电力学院 能源高效清洁利用广东普通高校重点实验室 广州 510640
- 折叠
摘要
Abstract
The influence of recirculated air and floating water on the performance of cooling tower in confined space remains to be further investigated. A thermodynamic model of cross cooling tower was set up and validated by the test with fully consideration of recirculated air. The influence of floating water on the simulation accuracy and recirculated air on the operation of cooling tower were analyzed. The re-sults show that the relative error of inlet air temperature and relative humidity are 14. 4% and 26%, respectively when floating water is not considered. The higher the recirculation ratio is, the greater the impact on cooling capacity of cooling tower becomes. The heat exchange capacity decreases 40. 68% when the recirculation ratio increases 50%.关键词
热力学模型/横流冷却塔/回流/飘水Key words
thermodynamic model/cross cooling tower/circumfluence/floating water分类
化学化工引用本文复制引用
马建荣,罗文海,夏少丹,蔡博达,吴疆,罗定鑫,冯腾飞,陈星龙,刘金平,刘雪峰..考虑回流的横流冷却塔热力学模型及运行特性分析[J].制冷学报,2014,(5):30-37,8.